Fluke 334A Clamp Meter
|
OUR PRICE: This unit has been discontinued. Please call (732) 632-6400 for replacement options.
Item Number: 334A
Manufacturer: FLUKE
Manufacturer Part No: 334A
|
Fluke 334A TRMS Clamp On Meter
Clamp meters that fit the way you work
- Three year warranty
- Small body and jaws fit perfectly in your hand and into
tight places
- Handy 'Display Hold' button keeps measurements on the
display
- Meter controls are positioned so current measurements can be
done with one hand (index finger on clamp opening lever and
thumb on rotary switch)
- Large, backlit display (on most models) is easy-to-see
- In-rush current function (on most models) for measuring starting
current for motors, lighting, etc.
- Auto shut-off maximizes battery life so the meter works when
you need it
- Improved low current measurement accuracy from new
microprocessor technology
- Five different models to meet your exact needs
|
Models:
- Fluke 333A - Rugged reliability at a basic price, measures
ac amps, ac/dc volts and ohms
- Fluke 334A - Large display with backlight, measures ac amps,
ac/dc volts, ohms and motor start-up current
- Fluke 335A - A True-rms clamp meter, large backlit display,
measures ac amps, ac/dc volts, ohms and motor start-up
current
- Fluke 336A - A True-rms clamp meter that measures ac/dc
current and voltage, ohms, motor start-up current with
large display and backlight
- Fluke 337A - The top-of the-line True-rms clamp meter,
large jaw measures ac/dc current and voltage, ohm,
motor start-up current (in-rush), frequency, MIN/MAX
capability and a large backlit display
|
|
Safety conformance: IEC 1010-2-032, 600V CAT III
Specifications:
|
Volatage DC
|
Range: 0-600.0 V
Accuracy: 1% ±5 counts
|
Voltage AC
|
Fluke 333A/334A
Range: 0-600.0 V
Accuracy: 1% ±5 counts (50/60 Hz)
AC Response: Averaging
Fluke 335A
Range: 0-600.0 V
Accuracy: 1% ±5 counts (50/60 Hz)
AC Response: True-RMS
Fluke 336A/337A
Range: 0-600.0 V
Accuracy: 1% ±5 counts (20-100 Hz),
6% ±5 counts (100-400 Hz)
AC Response Time: True-RMS
|
Current DC
|
Fluke 336A
Range: 0-600.0 A
Accuracy: 2% ±3 counts
Fluke 337A
Range: 0-999.9 A
Accuracy: 2% ±3 counts
|
Current AC
|
Fluke 333A/334A
Range: 0-400.0 A
Accuracy: 2% ±5 counts (50/60 Hz)
AC Response: Averaging
Fluke 335A
Range: 0-600.0 A
Accuracy: 2% ±5 counts (50/60 Hz)
Crest Factor (50/60 Hz): 2.4 @ 500A, 2.0 @ 600A, add 2% for CF>2
AC Response: True RMS
Fluke 336A
Range: 0-600.0 A
Accuracy: 2% ±5 counts (10-100 Hz),6% ±5 counts (100-400 Hz)
Crest Factor (50/60 Hz): 3 @ 500A, 2.5 @ 600A
AC Response: True RMS
Fluke 337A
Range: 0-999.9 A
Accuracy: 2% ±5 counts (10-100 Hz), 6% ±5 counts (100-400 Hz)
Crest Factor (50/60 Hz): 3 @ 500A, 2.5 @ 600A, 1.42 @ 1000A, add 2% for CF>2
AC Response: True RMS
|
Resistance
|
Fluke 333A
Range: 0-600.0 Ohm
Accuracy: 1.5% ±5 counts
Fluke 334A/335A/336A/337A
Range: 0-600.0 Ohm, 6001 - 6000 Ohm
Accuracy: 1.5% ± 5 counts
|
Frequency
|
Fluke 337A
Range: 5-400Hz
Accuracy: 0.5% ±5 counts
Trigger Level: 10-100 Hz >= 5A, 5-10 Hz, 100-400 Hz >=10A
|
Inrush Current
|
Fluke 334A/335A/336A/337A
Integration Time: 100ms
|
Continuity
|
<= 30 Ohm
|
MIN/MAX
|
Fluke 337A Only
|
Enviornmental Specifications:
|
Operating Temperature:
|
-10°C to 50°C
-14°F to 122°F
|
Storage Temperature:
|
-40°C to 60°C
-22°F to 140°F
|
Operating Altitude
|
2,500 meters max, 6,500 ft. max
|
Temperature
De-rating
|
Add 0.1 x specified accuracy for each °C above 28°C or below 18°C (above 82.4°F to 64.4°F)
|
Safety Specifications
|
Safety Rating
|
IEC 1010-2-032, 600V CAT III
|
Mechanical & General Specifications:
|
Size
|
Fluke 333A/334A/335A
240mm x 80mm x 40mm (9.375" x 3.125" x 1.625")
Fluke 336A/337A
250mm x 80mm x 40mm (9.875" x 3.125" x .625")
|
Weight
|
310 g (11 oz)
|
Warranty
|
Three years
|
Battery Life
|
Alkaline approximately 150 hours continuous
Automatic low battery indicator
|
Backlight
|
Fluke 334A/335A/336A/337A
|
Display Hold
|
Yes
|
|
Hard Instrument Carry Case with Pluck Foam to fit your instruments. 100's of sizes & styles available. Call for Details
|
|
|
|
|
Fluke H3 fabric holster that absorbs shocks and protects meter from rough handling. For use with Fluke 300 Series Clamp Meters.
|
| |
|
|